Conductor Options:
N2XY/C2XY:Copper to IEC 60228 Class 2
CA2XY:AA-8030 alloy (61% IACS)
Insulation System:
XLPE density:0.92g/cm³
Tanδ≤0.0008 (90℃)
Current Rating:
C2XY 4×185mm²:365A (in air)
CA2XY 4×185mm²:280A (in air)
|
|
|
|
|
|
Third-party Verified:
✓ VDE 0276 type approved
✓ IEC 60502-1 compliant
✓ C2XY-F:IEC 60332-3 Cat A
✓ CA2XY:IEC 62451 Al alloy standard
Precision Control:
① Online X-ray inspection (≥0.3mm)
② Continuous vulcanization (CV line)
③ Partial discharge <3pC
Critical Warnings:
⚠️ Soil thermal resistivity≤2.0K·m/W
⚠️ Separation≥200mm from HV cables
⚠️ Use torque wrench for terminals
Recommended:
• Cable pulling lubricant
• Anti-corrosion tapes
Container Loading:
20GP:10 drums (240mm² max)
40HQ:24 drums
• CE Declaration of Performance
• UL File E123456 (C2XY)
• CPR Class B2ca (N2XY)
BIM models (Revit format)
On-site jointing supervision
Cable management software